Kalos Services
Duct CheckHome airflow check

Duct & airflow check

Check an existing home: measure, check, improve.

AIRFLOW STARTING POINT350 CFM / ton
First principles / tech tipWhat this checks and how to use it

Use this to find possible problems—not to design a complete duct system. It does not calculate room heating and cooling loads, the blower’s operating point, the pressure used by every component, or the fitting losses along complete supply and return paths. Floor area alone cannot tell you a room’s load. Length alone cannot give the available friction rate for a full system.

Our starting approach: give ducts extra area to keep resistance and air speed low, put balancing dampers in the branches, and choose grilles or diffusers for the needed CFM, air speed and throw. Balance and check the installed airflow. Manual D covers duct sizing and balancing; outlet selection also needs the maker’s data and Manual T principles. Our extra stock-size margin and 25-ft length reference are Kalos troubleshooting choices, not ACCA sizing rules.

What a full Manual D design covers ↗

Start near the equipment. The supply plenum, return approach and filter carry the full system airflow. Check those first, then look at room branches and the paths back to the return.

Air amount, air speed, open space

CFM (cubic feet per minute) is how much air moves. FPM (feet per minute) is how fast it moves. Air speed = CFM ÷ clear area in square feet. At the same airflow, a larger clear opening slows the air. Sharp turns, crushed flex, filters and leaks still matter.

  1. Set the needed airflow

    In Equipment, use 350 CFM per ton or enter required CFM. A restriction can lower the measured airflow. Do not size the ducts for that lower airflow.

  2. Measure the air passage

    Enter outside dimensions for the default 1½-inch ductboard; the tool subtracts 3 inches from each dimension. Change material when needed. Use inside diameter for flex. Check the tightest clear return opening, too. Tap ? for measurement sketches.

    Example: 3 tons = 1,050 CFM. A 21 × 27-in. outside ductboard box is 18 × 24 in. clear inside: 3 ft², giving 350 FPM.

  3. Read the results in context

    Supply green is 350–550 FPM; return green is 350 FPM or less. Yellow needs review; red flags a concern. The colors do not tell you fitting pressure drop or prove the system meets the 0.50-in. w.c. pressure limit. in. w.c. means inches of water column, a pressure unit. Filter face area is a starting check. Use filter pressure drop to judge resistance. Use one cabinet or at most two external filters.

  4. Check room supplies

    Enter room CFM, or estimate from system CFM, house area, room area and load character. The area method gives each room a rough share of system airflow. It does not calculate the room’s heat load. Choose 1–3 supplies and throw distance. Branches get at least one common size above the minimum at 550 FPM. Enter the longest branch length when known; longer runs may need another size increase. Put dampers in the branches. Keep that margin and use a gradual reducer into a smaller confirmed boot collar; its air speed is shown separately. Slower air in a large branch can be useful.

  5. Size the path back

    Room returns and jump ducts follow the total intended supply CFM into the room. A jump duct needs enough open grille area at both ends. Suggested sizes do not guarantee room pressure: verify −3 to +3 Pa with the door closed. Pa means pascals, a pressure unit.

  6. Choose practical improvements

    Use Fittings & sizing to review tight openings, abrupt turns and flex routing. Check the throat (inside turn) as closely as the heel (outside turn). Check boot and collar fit, how far the register throws, and how much air reaches the room. Then balance the airflow. Open Field summary to copy the findings.

Field summary

Copying puts these notes on your device clipboard. Nothing is sent or submitted.

Measurement help